An efficient, streamlined, and easily deployableHydro-cooling module solution, ideal forwarehouse and container-based expansions.
Efficient Cooling
Efficient cooling capacity up to 200kW.
Suitable for 20 units of Whatsminer 2U hydro miner or 14 units of Antminer 3U
hydro miner.
All stainless steel core, high heat exchange efficiency, reliable and durable.
Modular Expansion
The smallest module for warehouse-style and container-style deployment.
Modular design, expandable to 200kW/400kW/600kW/800kW/1MW systems.
PLC-controlled modular management system.
Designed for Bitcoin Heat Recovery
Pre-designed heat exchanger interfaces with an optional stainless steel heat exchanger.
External cooling options include dry coolers or cooling towers.
Supports maximum outlet 80℃ water temperature, depending on the miners.

-
Features
- Temperature, flow, pressure, and leak sensors for multi-faceted monitoring.
- Proprietary 4-in-1 water tank, constant pressure, defoaming, refilling, heating.
- Automatic adjustment of pump and fan based on target temperature via PLC.
Automatic water refilling, pressure relief, and heating functions, ensuring worry-free startup of miners at low temperatures.
Flexible Power Scalability
The cabinet design supports modular power expansion from 200kW up to 1000kW, allowing mining farms to scale operations based on current demand and future growth—without the need for major infrastructure changes.
| Module | CDU | CDU | CDU | CDU | CDU |
| Size (H*W*D) | 2100mm * 600mm * 1000mm | 2100mm * 600mm * 1000mm | 2100mm * 800mm * 1000mm | 2100mm * 800mm * 1000mm | 2100mm * 800mm * 1000mm |
| Weight | 260KG | 310KG | 500KG | 514KG | 490KG |
| Rated Cooling Capacity | 200KW | 600KW | 800KW | 1000KW |
Single investment, double return.
- H200-S-3U
| Size | 800mm(W)*2100mm(H)*1050mm(D) |
| System Power Load (MAX) | 200kW |
| Miner Capacity | 14* Antminer U3S21EXPH |
| Input Voltage | 3-Phase 380V-415V, 50/60Hz |
| PDU | 20 Port SA2-30 Smart PDU |
| Network | 1000M Network Switch |
| Operation Temperature | -25℃~45℃ |
| Operating Humidity | 5%~95%RH |
| Water Manifold | Stainless Steel |
| Hose | PE/PTFE Hose + Quick Connects |
2. H200-CDU
| Size | 800mm(W)*2100mm(H)*1050mm(D) |
| Cooling Capacity | 200kW |
| Power | 3.5kW |
| Input Voltage | 3-Phase 380V-480V, 50/60Hz |
| Cooling Medium | Pure water/Soften water+Antifreeze
+Corrosion Inhibitor |
| Inlet/Outlet | 10°C (Normal)
14°C (High Performance) |
| Rated Flow Rate | 20m³/h |
| Operating Temperature | -25℃~45℃ |
|
Operating Humidity
|
5%~95%RH |
| PLC System | Constant flow control with pressure regulation |
| Communication Method | Modbus-RTU,TCP/IP |
| Design Pressure | 0.3MPa |
3. H200-Dry Cooler
| Model | FHWDC200 |
| Module | Dry Cooler V Type |
| Cooling Capacity | 200kW |
| Wight(Empty Load) | 800KG |
| FANs | 2 |
| Connection | DN50 |
| Fluid | Coolant |
| Fluid flowrate | 20m³/h |
| Inlet/Outlet Temperature | 55℃/40℃ |
| Ambient temperature | 35℃ |
| Fin/Tube Materials | 304 Stainless steel,Al-mg/AI |
| Operating/Maximum Pressure | 0.3MPA/1.6MPA |


Reviews
There are no reviews yet.